Multi circuit energy meter 
for IDC power monitoring
AMC16 series multi-circuit monitoring device of Acrel Company is a measuring device designed specifically for the power supply management of server in the data center. Such device is small and exquisite in design, capable of centralized monitoring on electric parameters and on-off states of dozens of circuits, including incoming line circuit and outgoing line circuit, and it achieves the highly integration of monitoring circuits in volume.

Specification
Technical Parameters
Technical parameters
AMC16Z-FAK24
AMC16Z-FAK48
Measurement parameters
Voltage, current, frequency, active power, reactive power, power factor, active power, reactive power, switching state
2-31 times harmonics
Bus voltage
Rated
220VAC
Measurement range
±20%
Overload
Instantaneous voltage 2 times/second
Current outgoing line loop
Rated
50mA
Range
0.125~60mA
Overload
Duration 1.2 times, instantaneous 10 times/second
Input frequency
45~60Hz
Measurement accuracy
Outgoing line
Voltage/current/active power/active energy level 0.5, reactive power/reactive energy level 1
Auxiliary power supply
Power supply by AMC16Z-ZA
Environment
Temperature
Working:-15℃~55℃ Storage:-25℃~70℃
Humidity
Relative humidity
Altitude
≤2500m
Communication
RS485/Modbus-RTU
Installation method
DIN35mm Guide rail or bottom plate mounting
IP grade
IP20
Class of pollution
2
Safety
Insulation
All terminals and the insulation resistance between the conductive pieces not below 100 m Ω
Withstand voltage
A-channel voltage and current signal // B-channel voltage and current signal // other ports meet AC2kV 1min between pairs, leakage
current should be less than 2mA, no breakdown or flashover phenomenon.
Electromagnetic compatibility
Anti static interference
Level 4
Resistance to radiation of radiofrequency electromagnetic field
Level 3
Remote Power Panel For Internet Data Center (IDC)
Customized service
If you have any special requirements, for example special diagram and special power supply, or you need the whole Remote Power Panel for IDC monitoring ,please feel free to Contact Us.
Dimensions
Certifications
Packing & Delivery
Company Profile
Acrel Electric Co., Ltd. [Stock Code: 300286.SZ]
Founded in 2003, one of the few leading companies in China who provides various systematic solutions of power monitoring, power control, energy management and electrical safety for smart grid users. Substation automation system, power quality management system, energy management system, electrical fire monitoring system, IT distribution system for medical locations, precise distribution management system, FEPS power supply monitoring system, fire emergency lighting and evacuate indicating system, smart lighting control system and electric vehicle charging system.
FAQ

Q: Are you trading company or manufacturer ?

A: We are factory. Warmly welcome you to visit and investigate our factory.

Q: How long is your delivery time?

A: Generally it is 3-10 days if the goods are in stock. or it is 10-20 days if the goods are not in stock, it is according to
quantity.

Q: Do you provide samples ? is it free or extra ?

A: Yes, we could offer the sample for lower price. If you place the order, all or part of the sample charge will be deducted from the goods. Please contact us.

Q: What is your terms of payment ?

A: Usually, 100%TT in advance. If you have projects for another payment terms, please feel free to contact us as below:
Contact Us