Welcome to wziep.com!
Welcome to wziep.com!
category: Power Distribution Equipment
reference price:¥$20,000.00
Standard | IEC 62271-1 |
IEC 62271-202 | |
IEC60067 | |
IEC61439 | |
No. of medium voltage compartment | 1 |
No. of transformer compartment | 1 |
No. of low Voltage compartment | 1 |
Medium voltage compartment | |
Protection spec | IP43 |
Service Rated voltage | 15KV |
Voltage variation of the system | ±10% |
Permisible maximum operating voltage | 17.5KV |
Permisible maximum Equipment voltage | 24Kv |
RMU(2 incomming + 1 outgoing) | |
Load break switch with earthing switch | 2 |
Type | |
frequency | 50Hz |
Power frequency withstand voltage(RMS) | 38KV |
Rated lightning impulse withstand voltage (Peak) | 95KV |
Rated current | 630A |
Rated short time withstand current for 1s | 25KA |
Vacume circuit breaker with earthing switch and isolator | 1 |
Nominal voltage | 15KV |
rated frequency | 50Hz |
Power frequency withstand voltage(RMS) | 38KV |
Rated lightning impulse withstand voltage (Peak) | 95KV |
Rated short time withstand current for 1s | 25KA |
Low Voltage compartment | |
Protection spec | IP23 |
Nominal voltage | 0.4KV |
rated frequency | 50Hz |
Power frequency withstand voltage(RMS) | 3KV for 1 minute |
Rated current | 1250A |
Rated short time current rating | 50KA |
CT quantity | 3 |
CT voltage rating | 380V |
CT Ratio | 1250/5A |
Freq. | 50Hz |
Burden | 15VA |
Ammeter quantity | 3 |
ammeter current range | 0-1250A |
Voltmeter with selector switch quantity | 1 |
voltage range | 0-500V |
Tansformer compartment | |
Protection spec | IP23 |
Cooling method | ONAN |
No of Phases | 3 |
Standard | IEC 60354 |
Freq. | 50Hz |
Rated contineous power on HV side | 630KVA |
Rated contineous power on LV side | 630KVA |
Rate voltage on HV side | 15Kv |
Rate voltage on LV side | 0.4Kv |
Vector group | Dyn5 |
No load loss at rated voltage and frequency | <=0.6KW |
Full load loss | <=6.5KW |
Color | Gray |
Thickness of surface treatment | 140µm |
short circuit impedance at principal tapping | 4% |
ability to withstand unbalanced load | >=9% |
Transformer tank | steel |
Core type | steel |
type | wire or coil |
HV winding material | copper |
Power frequency withstand voltage(RMS) | 38KV |
Rated lightning impulse withstand voltage (Peak) | 95KV |
LV winding material | copper |
Power frequency withstand voltage(RMS) | 3KV |
Rated lightning impulse withstand voltage (Peak) | 6KV |