category: Energy Management System
Function | APM800 (class 0.5s) | APM801 (class 0.2s) | APM810 (class 0.5s) | ||||
Measured parameters | Total electrical measurement | √ | √ | √ | |||
Four-quadrant energy | √ | √ | √ | ||||
Pulse output of energy | √ | √ | √ | ||||
Demand | Three-phase current, active power, reactive power, real-time demand of apparent power, and maximum demand (including time stamp) | √ | √ | √ | |||
Extreme value statistics | Extremum of current, line voltage, phase voltage, active power, reactive power, apparent power, power factor, frequency, total harmonic of current, total harmonic of voltage in this month and last month (including time stamp) | √ | √ | √ | |||
Power quality | Unbalance of current, line voltage, phase voltage | √ | √ | √ | |||
Voltage phase angle, current phase angle | √ | √ | √ | ||||
Voltage current phase Angle | √ | √ | √ | ||||
Total (odd, even) harmonic content of voltage and current | × | × | √ | ||||
Harmonic content of voltage and current (2-63 times)① | × | × | √ | ||||
Voltage crest factor | × | × | √ | ||||
Telephone waveform factor | × | × | √ | ||||
Current K-factor | × | × | √ | ||||
Alarm records | A total of 66 kinds of alarm types, each type can record the most recent 16 alarm records, support extended records by TF card | √ | √ | √ | |||
Event log | Record the most recent 128 event records, support extended records by TF card | √ | √ | √ | |||
Communication | Modbus protocol | √ | √ | √ | |||
I/O | 2 digital inputs + 2 digital outputs (2DI+2DO) | √ | √ | √ | |||
Extensions | MD82 | 8 digital inputs + 2 digital outputs with changeover contacts (8DI+2DO) | √ | √ | √ | ||
TF card storage (alarm records, event records, electrical parameters and energy timing records, etc.) | √ | √ | √ | ||||
MA84 | 8 analog inputs (class 0.5) + 4 analog outputs (class 0.5) (8AI+4AO) | √ | √ | √ | |||
MCM | 1 RS485/Modbus-RTU, support master mode or slave mode | √ | √ | √ | |||
MCP | 1 Profibus-DP | √ | √ | √ | |||
MCE | 1 Ethernet, support Modbus-TCP, http, SMTP, DHCP protocol | √ | √ | √ | |||
4 ways of temperature measurement, 1 way of temperature and humidity control | √ | √ | √ |
Function | APM830 (class 0.5s) | ||||
Measured parameters | Total electrical measurement | √ | |||
Four-quadrant energy | √ | ||||
Complex rate electric energy | √ | ||||
Internal temperature measurement of instrument | √ | ||||
Pulse output of energy | Total active power, total reactive power, total apparent power pulse output, second pulse, etc | √ | |||
Demand | Three-phase current, active power, reactive power, real-time demand of apparent power, and maximum demand (including time stamp) | √ | |||
Extreme value statistics | Extremum of current, line voltage, phase voltage, active power, reactive power, apparent power, power factor, frequency, total harmonic of current, total harmonic of voltage in this month and last month (including time stamp) | √ | |||
Power quality | Unbalance of current, line voltage, phase voltage | √ | |||
Voltage phase angle, current phase angle | √ | ||||
Total (odd, even) harmonic content of voltage and current | √ | ||||
Harmonic content of voltage and current (2-63 times)① | √ | ||||
Voltage crest factor | √ | ||||
Telephone waveform factor | √ | ||||
Current K-factor | √ | ||||
Vector | √ | ||||
Voltage and current waveform | √ | ||||
Fundamental voltage and current | √ | ||||
Alarm records | A total of 66 kinds of alarm types, each type can record the most recent 16 alarm records, support extended records by TF card | √ | |||
Event log | Record the most recent 128 event records, support extended records by TF card | √ | |||
Transient record, record up to 800 transient waveform records, support TF card expansion record | √ | ||||
Communication | Modbus-RTU protocol | √ | |||
DL / T 645 - 2007 protocol (support freeze function) | √ | ||||
I/O | 2 digital inputs + 2 digital outputs (2DI+2DO) | √ | |||
Multiple rate | The multi-rate energy statistics include total, sharp, peak, flat, valley and near-month multi-rate electricity | ||||
Extensions | MD82 | 8 digital inputs + 2 digital outputs with changeover contacts (8DI+2DO) | √ | ||
TF card storage (alarm records, event records, electrical parameters and energy timing records, etc.) | √ | ||||
MA84 | 8 analog inputs (class 0.5) + 4 analog outputs (class 0.5) (8AI+4AO) | √ | |||
MCM | 1 RS485/Modbus-RTU, support master mode or slave mode | √ | |||
MCP | 1 Profibus-DP, Configure this function to give MCM function, referred to as MCMP for short. | √ | |||
MCE | 1 Ethernet, support Modbus-TCP, http, SMTP, DHCP protocol,Configure this function to give MCM function, referred to as: MCME | √ | |||
4 ways of temperature measurement, 1 way of temperature and humidity control | √ |
Technical Parameters | Index | ||||
Signal | Electrical network | Three-phase three-wire, three-phase four-wire, see the wiring diagram; | |||
Frequency | 45~65Hz; | ||||
Voltage | Rated value:AC 100V、110V、400V、690V; | ||||
Overload: 1.2 times rated value(continuous); 2 times rated value /1 second; | |||||
Power consumption: < 0.5VA (per channel); | |||||
Current | Rated value: AC 1A, 5A, support 4 mm2 line access; | ||||
Overload: 1.2 times rated value(continuous); 10 times rated value/1 second; | |||||
Power consumption: < 0.5VA (per channel); | |||||
Measurement accuracy | Voltage、current and power | ||||
Active power | class 0.5s/class 0.2s (APM800、APM810/APM801) | ||||
Reactive power | class 2 | ||||
Harmonic | 1%(2rd~42nd)、2%(43rd~63rd) | ||||
Switch inputs | Dry contact inputs, built-in power supply; | ||||
Relay outputs | Contact type: open contact in main part, changeover contact in module; Contact capacity:AC 250V/3A DC 30V/3A; | ||||
Pulse output of energy | Output mode: Optocoupler pulse with open collector; Pulse constant:4000(5A)、8000(1A) imp/kWh; | ||||
Analog outputs | DC 0mA~20mA、4mA~20mA、0V~5V、1V~5V output, accuracy class 0.5%, load resistance ≤ 500Ω; | ||||
Analog inputs | DC 0mA~20mA、4mA~20mA、0V~5V、1V~5V iutput, accuracy class 0.5% | ||||
Storage card | Standard Capacity:4G,TF Card Up to 32G Capacity; | ||||
Communication | RS485 interface/Modbus-RTU protocol and DLT645 protocol Profibus-DP interface/Profibus-DP protocol; RJ45 interface (Ethernet) / Modbus-TCP, http, DHCP and other protocols; | ||||
Power supply | Working range: AC/DC 85V~265V or AC/DC 115~415V(P2); Power consumption: Power consumption of the main part ≤ 15VA; | ||||
Safety | The power frequency withstand voltage between the shell and the auxiliary power supply, each input and output terminal group is AC 4kV/1min; The power frequency withstand voltage between the auxiliary power supply and each input and each output terminal group is AC 2kV/1min; The power frequency withstand voltage between the voltage input and other input/output terminal groups is AC 2kV/1min; The power frequency withstand voltage between the current input and other input/output terminal groups is AC 2kV/1min; The power frequency withstand voltage between the relay output and other input/output terminal groups is AC 2kV/1min; The power frequency withstand voltage between each terminal group of switch input, communication, analog output and pulse output is AC 1kV/1min; | ||||
Insulation resistance | Inputs、outputs to the shell>100MΩ; | ||||
Electromagnetic compatibility | Meet IEC 61000 standard (Level 4); | ||||
Environment | Operating temperature: -20 °C ~ +65 °C; Storage temperature: -20°C~+70°C; Relative humidity: ≤95% without condensation; Altitude: ≤2500m; | ||||
Standards | IEC 60068-2-1 IEC 60068-2-2 IEC 60068-2-30 | Environmental Testing-Part 2-1:Tests Test A:Cold IDA Part 2-1:Tests Test B:Dry heat Part 2-30:Tests Test Db:Damp heat,cyclic(12+12h) | |||
IEC 61000-4 | Electromagnetic compatibility-Testing and measurement techniques | ||||
Electrical safety in low voltage distribution system up to 1000V a.c. and1500V d.c –Equipment for testing,measuring or monitoring of protective measures- Part12: Performances measuring and monitoring devices(PMD) | |||||
Electricity metering equipment (a.c.)-Particular requirements - Part22:Static meter for active energy(class 0.2s and 0.5s) |
Technical Parameters | Index | ||||
Display | Display method | Dot matrix LCD | |||
Resolution | 192 * 160 | ||||
Backlight | White LED | ||||
Visible area | 69mm*62mm(2.8Inch / 6.66inch) | ||||
Signal | Electrical network | Three-phase three-wire, three-phase four-wire, see the wiring diagram; | |||
Frequency | 45~65Hz; | ||||
Voltage | Rated value:AC 3*57.7/100V、AC 3*63.5/110V、AC 3*230/400V、AC 3*400/690V;690V direct connection on voltage input terminal(L-L) | ||||
Overload: 1.2 times rated value(continuous); 2 times rated value /1 second; | |||||
Power consumption: < 0.5VA (per channel); | |||||
Current | Rated value:AC 3x 1 (1.2) A、AC 3x5(6)A, support 4 mm2 line access; | ||||
Overload: 1.2 times rated value(continuous); 10 times rated value/1 second; | |||||
Power consumption: < 0.5VA (per channel); | |||||
Measurement accuracy | Voltage、current | IEC 61557-12 class 0.2 | |||
Voltage imbalance | IEC 61557-12 class 0.2 | ||||
Voltage harmonics, current harmonics | |||||
frequency | IEC 61557-12 class 0.2s | ||||
Active power | IEC 61557-12 class 0.2s | ||||
Reactive power | IEC 61557-12 class 1s | ||||
inspecting power | IEC 61557-12 class 0.2 | ||||
Active energy | IEC 62053-22 - Active energy 0.2S | ||||
Reactive energy | IEC 62053-24 - Reactive energy 0.5S | ||||
Power Quality | Recording wave | 20 waveforms, 10 waves before and after; | |||
Waveform capture | Each waveform is stored at 128 cycle points; the TF card is supported to expand the recorded data, and the customer needs to manually pull the line chart through Excel. | ||||
Switch inputs | Dry contact inputs, built-in power supply; Response time: less than 300ms | ||||
Relay outputs | Contact type: open contact in main part, changeover contact in module; Contact capacity:AC 250V/3A DC 30V/3A; | ||||
Pulse output of energy | Output mode: Optocoupler pulse with open collector; Pulse constant:10000imp/kWh(default),For details, see 6.2 Input Settings.; | ||||
Analog outputs | DC 0~20mA、4~20mA、0~5V、1~5V Output, accuracy grade 0.5%, load resistance ≤500Ω at current output, load resistance ≥2KΩ at voltage output; overload: 1.2 times rated value (continuous); | ||||
Analog inputs | DC 0~20mA, 4~20mA, 0~5V, 1~5V input, accuracy grade 0.5; overload: 1.2 times rated value (continuous); | ||||
TF Storage card | Standard TF card with 4G capacity, maximum support for TF card with 32G capacity; | ||||
Communication | RS485 interface/Modbus-RTU protocol and DLT645 protocol Profibus-DP interface/Profibus-DP protocol; RJ45 interface (Ethernet) / Modbus-TCP, http, DHCP and other protocols; | ||||
Power supply | Working range: AC/DC 85V~265V or AC/DC 115~415V(P2); Power consumption: Power consumption of the main part ≤ 15VA; | ||||
Safety | The power frequency withstand voltage between the shell and the auxiliary power supply, each input and output terminal group is AC 4kV/1min; The power frequency withstand voltage between the auxiliary power supply and each input and each output terminal group is AC 2kV/1min; The power frequency withstand voltage between the voltage input and other input/output terminal groups is AC 2kV/1min; The power frequency withstand voltage between the current input and other input/output terminal groups is AC 2kV/1min; The power frequency withstand voltage between the relay output and other input/output terminal groups is AC 2kV/1min; The power frequency withstand voltage between each terminal group of switch input, communication, analog output and pulse output is AC 1kV/1min; | ||||
Insulation resistance | Inputs、outputs to the shell>100MΩ; | ||||
Electromagnetic compatibility | Meet IEC 61000 standard (Level 4); | ||||
Environment | Operating temperature:-25℃~+70℃; Storage temperature:-40℃~+85℃; Relative humidity:≤75% without condensation; Altitude:≤2000m; | ||||
Protection Level | Display panel IP54, with gasket; | ||||
Standards | IEC 60068-2-1 IEC 60068-2-2 IEC 60068-2-30 | Environmental Testing-Part 2-1:Tests Test A:Cold IDA Environmental Testing Part 2-2:Tests Test B:Dry heat Environmental Testing Part 2-30:Tests Test Db:Damp heat,cyclic (12+12h) | |||
IEC 61000-4 | Electromagnetic compatibility-Testing and measurement techniques | ||||
Electrical safety in low voltage distribution systems up to 1 000V a.c. and 1 500V d.c –Equipment for testing, measuring or monitoring of protective measures — Part12:Performances measuring and monitoring devices(PMD) | |||||
Electricity metering equipment (a.c.)-Particular requirements - Part 22: Static meter for active energy(class 0.2S and 0.5S) | |||||
Electricity metering equipment (a.c.)-Particular requirements - Part24:Static meter for reactive energy at fundamental frequency (classes 0.5S 1S and 1) |