DD100TEFR LED display three phase four wire electronic DIN-rail multi-tariff active energy meter,RS485 communication

category: Energy Meters

reference price:¥$5.00 - $30.00

Purchase quantity
- +

Fato Mechanical And Electrical Co., Ltd.

Mr. Zheng
Product details Company introduction
Parameter information

DD100TEFR LED display  three phase four wire electronic DIN-rail multi-tariff active energy meter,RS485 communication

APPLICATION

 

The meter is used to measure 50Hz or 60Hz active energy consumption from three phase four wire AC electricity net.

The features of small size & DIN-rail mounting make it suitable for installation in distribution boards and small standard enclosures.

The meter is widely used in the office buildings, shopping malls, residences, airports and metro,etc.

The meter has function of different tariff measure for different time period. The RS485 communication module in it makes it convenient to meter-reading.

 

FEATURES & FUNCTIONS

 

 35mm standard DIN rail installation,complying with standard DIN EN50022.Or front board installed (mounting holes center distance 63 mm), users can choose any one by themselves.

Seven poles width.

LED 5+2 digits display (99999.99kWh).

Standard configuration one port of pulse output passive (polarity),may select increase a distant port of pulse output passive   

(nonpolarity),complying with standard IEC 62053-31 and DIN 43864.
LED indicates respectively power-supply,impulse,and communication,etc.
Automatically detect the direction of the trend of load current. If the LED REV lights that means the load current is reverse.
Single direction three components measure three phase four wire active energy consumption. It is nothing with direction of the flow of 

load current,complying with standard IEC62053-21,IEC62052-11.

May select two components measure three phase three wire active energy or two phase three wire active energy.

♦Multi-tariff is available (optional TOU or step tariff).

♦RS485 output interface (optional) enable remote data transfer,remote -control reading and parameter setting.

Direct connect operation or through CT or PT & CT.

Standard configuration short terminal cover, which is helpful to reduce installation space and make it convenient to installMay select extended terminal cover.

 

TECHNICAL PARAMETER

 

Accuracy

Class 1.0

Rated voltage(VAC)

3*57.5/110,  3*110/200,  3*220/380,  3*230/400,  3*240/415,etc.

Operation voltage range 

Un±20%

Insulation capabilities

AC voltage withstand 2kV for 1 minute;Impulse voltage withstand 6kV - 1.2/50μs waveform

Rated current(A)

1.5(6), 5(30), 10(60), 20(80), 30(100),etc.

Operation current range

0.05Ib~ Imax

Starting current 

0.004Ib

Rated frequency

50Hz or 60Hz

Internal power consumption

Voltage circuit ≤1.0W 5VA;   Current circuit ≤1VA(Ib)

Impulse valence Ra

0.5 or 1.0 Wh/imp 

Interface

optical coupler (SO corresponding to DIN 43864)

RS 485 communication

Baud rate:1200bps (default)

Remote pulse output

Pulse width: 80ms ± 20ms

Temperature Range

Normal operation temperature: -35ºC--+70ºC

Extreme operation temperature: -40ºC--+75ºC

Storage Temperature: -45ºC--+85ºC

Relative humidity

 85%

Service Life

More than 10 years

Dimension

125mm x 88mm x 73mm

Weight

Approx 650g

*Please advise us if you need any different specifications, we can make according to your special requirements.

 

  

DIMENSION

 

 

WIRING

 

 

 

OUR COMPANY

 

CERTIFICATIONS