Categories

led display three phase row recording meter voltage frequency meter

category: Voltage Meters

Purchase quantity
- +

Zhejiang Huapu Instrument Co., Ltd.

Mr. Zj
Product details Company introduction
Parameter information

Product Description

Summarization

Product name

 Digital meter
Display typeRed LED
 Size96*96mm
 Accuracy±0.5% FS
Aux. power supply AC 220V or AC/DC 85 ~ 264V
 Weight 200g
 Overload  Continuous: 1.2 times, instantaneous: 2 times/1s
 Colour Black or white
 Analog quantity output mode 0~20mA, 4~20mA, can be programmable
 Working temperature-10~55°C

led display three phase row recording meter voltage frequency meter

 

 Basic Specification

Technical parameterIndex value

Accuracy of

measurement

Current / voltage±0.5% FS

Active/reactive/apparent power

±0.5% FS
Frequency±0.1Hz
Power factor±0.01PF
Active energyGrade 1.0
Reactive energyGrade 2.0
Power supplyRangeAC/DC 85~264V
Power consumption< 5VA
Input        Network3P3W, 3P4W
Voltage   Rated voltageAC 57.7V, 100V, 220V, 380V
OverloadContinuous: 1.2 times (if exceed, display HHHH), instantaneous: 2 times/1s
Power consumption<1VA (each phase)
Impedance>1kΩ/V
Current  Rated currentAC 1A ,5A
Overload Continuous: 1.2 times (if exceed, display HHHH), instantaneous: 10 times/5s
Impedance <20mW (each phase)
Frequency range  45 ~ 65Hz
 Output           Energypulse  Output mode  1-channel collector open coupling pulse output
 Pulse constant3200imp/kWh

 RS-485

Communication 

 Agreement MODBUS_RTU
 Baud ratio 1200, 2400, 4800, 9600, 19200

Analog

 quantity  

 Channel number 1-channel or 3-channel (some types can support 4-channel)
 Output mode 0~20mA, 4~20mA ,can be programmable
 Load capacity ≤500Ω

Switching

value  

 Channel number 1-channel or 3-channel (some types can support 4-channel)
 Output method The upper and lower limits use the same relay (No contacts) to output
 Contact capacity AC 240V/1A
 Switching value input  1 or 3-channel (some types can support 4-channel) passive contact
 Safety  Insulation resistance  Among the input, output, power supply and shell >20MΩ
 Withstand voltage  Among the input, output and power supply ≥ 2kV 50Hz/1min
 Environment  Temperature  Working: -10~55℃, storage: -25~70℃
 Humidity  ≤85%RH, places without condensation corrosive gas situation

led display three phase row recording meter voltage frequency meter

 

Contour & Installation Size     unit:  mm

Meter SizeSurface SizeShell SizeInstallation Size
Width (D)Height (H)Width (D)Height (H)Depth (L)Width (D)Height (H)
120 square12012011011080112112
80 square80807575807676
72 square72726767856768
96 square96969191809292

led display three phase row recording meter voltage frequency meter

 

Application

Company Information

Certifications

 

Our Team

Show Room

Packaging & Shipping

 

Contact Us