Product Description
The automatic recovery over voltage and under voltage protective device complies with modular design standards. the circuit boards of products adopt good quality electronic components with reliable performance. when the power situation is unstable. It's protection function will be automatically activated. once the voltage exceeds the limited range of products, it will automatically cut off so as to protect the safely of electrical equipment and persons.

Functions:

1.Over-voltage protection

2.Under-voltage protection

3.Over-current protection

4.Automatic recovery

5.Voltage display(voltage measurement)

6.Current display (current measurement)



Product Parameters:

1.Model number:TVPS1-63B

2.Power supply:230VAC 50/60Hz

3.Max.Loading power:1~40A Adjustable(default:40A)

1~63A Adjustable(default:63A)


4.Over-voltage protection value range:221V~300~OFF(default:280V)

Over-voltage recovery voltage range:220V--299V(default:250V)

Over-voltage protection action time:0.1s~10s(default value:0.1s)


5.Under-voltage protection value range:219V--150V --OFF(default:160V)

Under-voltage recovery voltage range:151V--220V (default:180V)

Under-voltage protection action time:0.1s~10s(default:0.1s)


6.Over-current adjustment range:1-40A (default:40A)
Over-current action range:0.1~512 second (default:5.0s)


7.Recovery delay time:2s~120s(default:60s)​​

8.Power-on delay time:2s~10s(default:2s)

9.Power consumption : <2W

10.Electric machinery life : 100,000 times

11.Installation:35mm DIN rail

Noted: When you first connect the product, you have to wait about 1 minute, after the red light turn off, then the product will