Categories

FORERUN FJK-02-12F Intelligent reactive power compensation of power factor controller 138*138

category: Power Factor Controller

reference price:¥$58.00

Purchase quantity
- +

Shijiazhuang Furun Zhongcheng Trading Co., Ltd.

limei
Product details Company introduction
Parameter information
Product Description
Product name
Intelligent Reactive Power Compensation Controller
Product model
FJK-02-12F
Product introduction
FJK-02 intelligent reactive power compensation controller is suitable for automatic adjustment of capacitor compensation device in
low-voltage distribution system (controller for short). It enables power factor to reach user's preset state, improves utilization
efficiency of power transformer, reduces line loss and improves power supply quality, thus improving economic benefits and social
benefits.
Functional characteristics
1. Fully digital design, AC sampling. The human-machine interface adopts large-screen LCD and Chinese liquid crystal display.
2.Adhering to the people-oriented design concept, modular assembly and streamline design. 
3. Real-time display of power factor,voltage, current, active power, reactive power, total harmonic distortion rate of voltage, total harmonic distortion rate ofcurrent, frequency, temperature, capacitance output display, switching status alarm and other information of L1, L2 and L3 phases.
4. Set Chinese prompt for parameters and enter numbers. 
5. Capacitor control scheme supports three-phase compensation, split-phasecompensation and comprehensive compensation scheme. Control scheme can be set through menu.
6. It has two working modes of manualcompensation/automatic compensation. 
7. The sampling physical quantity is reactive power and has harmonic measurement andprotection functions.
Appearance size
Opening size: 138mm*138mm
Overall dimensions: 144mm*144mm*104mm
Product name
Reactive compensation controller
model
FJK-02-12F
Control the number of switching paths
12
Compensation type
Hybrid compensation
Opening size
138*138 mm
Related Products














product wiring
Terminal description
Terminal label
state
Explain
Remarks
Ua、Ub、Uc
input
It is three-phase sampling voltage respectively; at the same time, Ub and UC are multiplexing of working power supply of the
machine
The power supply is 380V AC
Un
input
Zero line
Sampling zero line
IA、Ia、IB、Ib、IC、Ic
input
Sampling current transformer input
Respectively from three-phase La, LB and LC current transformers
COM
output
Internal 12V power output +
Connected to 12V + terminal of SCR trigger module / composite switch
K1~K12
input
Control terminal of output from the first group to the twelfth group
Connected to 12V terminal of SCR trigger module / composite switch
A、B
communication interface
MODBUSAgreement
Conditions of use
1. Altitude: ≤2500m
2. Operating temperature: 65123; 30℃ ~+55℃
3. Storage temperature: 65123; 35℃ ~+60℃
4. No corrosive gas, no conductive dust and no inflammable and explosive medium.
5. The installation site shall be free from severe vibration and rain and snow erosion.
Technical parameter
1. measuring voltage: 100 v ~ 290 v
2. Measuring current: 0 ~ 6000A
3. Measuring power factor: lag 0.200 ~ lead 0.200
4. Operating power supply: 380 V 20%
5. Measurement frequency: 47 ~ 53Hz
6. Sensitivity: 50mA
7. Display active power: 0 ~ 6553 kW
8. Display reactive power: 0 ~ 6553 kVAR
9. Display voltage total harmonic distortion rate: 0.0 ~ 50.0%
10. Display current total harmonic distortion rate: 0.0 ~ 100.0%
Input/output signal
1. sampling voltage: La, Lb, Lc phase voltage
2. sampling current: bus La, Lb, Lc phase current transformer secondary 0 ~ 5a
3.12V 40mA/ branch
Note: The sampling voltage and sampling current must be in phase!
Display performance
LCD liquid crystal display data display refresh period ≤1s
Communication interface data

1.Communication interface: RS-485
2. Protocol: MODBUS communication protocol
3.communication rate: 4800~38400bps (no parity bit)
Measurement accuracy
1. Voltage: 0.5%
2. Current: 0.5%
3. Active power: 1.0%
4. Reactive power: 1.0%
5. Power factor: 1.0% 6. Frequency: ±0.1Hz
Set data range
1. Temperature setting: 40 ~ 100 C (temperature protection value)
2. .Delay time: D1: 0.1s ~ 300sd2: 0-300s
3. . overvoltage setting: 235 v ~ 280 v
4. Switching threshold:: 0.5 ~ 1.2 (the set value is the switching threshold) Step size: 0.1
5. .Removal Threshold-1.2-Current Setting
6. current change ratio: 1 ~ 1000 (ratio value)
7. Target COSΦ φ: lag 0.85 ~ lead 1.00
8. Undervoltage setting: 175 V ~ 210 V, or off
9. Harmonic protection: HV: 0.0% ~ 100.0% (0.0% off) HI: 0.0% ~ 100.0% (0.0% off)
The compensation mode and capacity of each channel of capacitor can be arbitrarily set as required..
Capacitor preset: 0 ~ 250kvar/group
ID number setting
This machine has communication interface and supports MODBUS protocol. This item includes ID number and communication rate setting
of 485 communication interface. ID number is the address number 001 ~ 255
describing this machine in the system network. Communication rate: 4800~38400bps Reliability: mean time to failure (mtbf): > 25000
hours
Certifications
Packing&Shipping
Company Introduction
Shijiazhuang Furun Zhongcheng Trading Co., Ltd. is located in Chang'an District, Shijiazhuang City, Hebei Province. Is a diversified electronic product sales enterprise, with a professional management team, a wide range of industry background, professional financing institutions, in the national range has a perfect marketing and service network. The sales service area covers 20 provinces and cities in China and has established close cooperation with them. In the development of the company, we do not forget to optimize customer service. With strong economic and technological strength, high-quality professionals and high-quality and efficient services, we have established a good corporate image in the society, which has been widely trusted and praised by all walks of life and customers. We have won the highest evaluation of new and old customers with the same enthusiasm!