DL7NL-40 dl rcbo circuit breaker 6ka top and button with SAA & ESV for Australian standard

Notice: The following picture is 3KA RCBO, its principle is same as 6KA RCBO.

 

 

Scope of application

 

DL7NL-40 earth leakage circuit breakers are mainly applied to the AC 50Hz/60Hz circuit rated 240V and 40A or below, They have the electric leakage (electric shock), overload, short circuit and so on protection functions. The over voltage protection function can also be provided upon requirements. They are mainly used to protect the building illumination and power distribution system.

 

Specifications

 

Rated Voltage (V)

Rated Current (A)

In (mA)

In o (mA)

  Break time

Icn, Ics 

Im (A)

I

2 In

0.25A

500A

240

6,10,16,20,25,

32,40

30,100

15,50

≤0.1

≤0.05

≤0.04

≤0.04

6kA

2000

 

Main Technical Parameters

 

Testing Current

Rated Current(A)

Initial state

Testing Time ( T )

Testing Result

Note

6,10,16,20,25,32,40

1.13In

Cold State

≥1h

Not Tripped

 

1.45In

Thermal State

<1h

Tripped

Current stably rise to specified value in 5s.

2.55In

Cold State

1-60s

Tripped

 

Tripper Type

B

3In

Cold State

≥0.1s

Not Tripped

 

5In

Cold State

<0.1s

Tripped

 

C

5In

Cold State

≥0.1s

Not Tripped

 

10In

Cold State

<0.1s

Tripped

 

D

10In

Cold State

≥0.1s

Not Tripped

 

50In

Cold State

<0.1s

Tripped

 

 

Installation and the wiring diagram

Install breaker

 

Take down breaker

 

  1. Push down the DIN rail, installing the card
  2. Tilt over the device and raise it up

Note: It will be locked when you pull out the rail installing card, so, before installing the device onto the DIN rail again, you should push it inward.

 

Combined with the other same type product

 

The advantage of DL7NL-40: it takes double modulus

The advantage of DL7NL-40: breaking capability is 6kA